5.5

Temperature control

5.5.1
General
Displays only the functions enabled in configuration 1 or configuration 2. All other
functions are hidden. General there is a mix of use of exhaust and return air
sensor!
Main Index > Unit > Temp control
Function
Present temperature used for control. Eight supply air, room or return tempera-
ture depending on the setting and control type.
Go to setpoint page with all setpoints affected by temperature control, e.g. com-
fort, economy, cascade min max, deviation alarm, summer-winter compensation.
Displays heating and cooling setpoint. Go to cascade controller page with de-
tailed settings.
Go to page for min/max ctlr sply to parameterize the minimum and maximum limit
controller. You can use the existing supply air sensor to limit the minimum or
maximum allowable supply air temperature if purely room or return air control is
active.
Present value of the mixed aid damper control. Go to parameter page for mixed
air damper control.
Present value for heat recovery control. Go to parameter page for heat recovery
control.
Present value for heating register control. Go to parameter page for heating regis-
ter control.
Present value for electrical heating register control. Go to parameter page for
electric heating register control.
Present value for cooling register control. Go to parameter page for cooling regis-
ter control.
Present value for heating register control for an additional register. Go to parame-
ter page for heating register control.
Present value for electric heating register control for an additional register.
Go to parameter page for electric heating register control.
Present value for cooling register control for an additional register. Go to parame-
ter page for cooling register control.
Present value of the fan heating sequence. Go to parameter page for fan heating
sequence.
Present value of the fan cooling sequence. Go to parameter page for fan cooling
sequence.
Present value of the fan temperature compensation. Go to parameter page for
fan temperature compensation.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Functions
59 / 244
CE1P3977en_02
Page 59
01.02.2010