Siemens Climatix Series Basis Document page 201

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Temp control > Heat recovery > Frost protection
Parameter
Function
Controller
Output from loop controller; Jumplin to
settings
Setpoint
Setpoint for Frostcontroller
Main Index > Unit > Temp control > Heat recovery > Frost protect press
Parameter
Function
Controller
Output from loop controller; Jumpline to
settings
Fan stage 1 stpt
Frost Setpoint if Fan Stage 1 is active
Fan stage 2/3 stpt
Frost Setpoint if Fan Stage 2 or 3 is active
Main Index > Unit > Temp control > Heating
Parameter
Function
Controller
Heating Controller; Jumpline to settings
Output signal
Heating Valve Position; Jumpline to settings 0...100
Frost protection
Actual Value; Jumpline for Frost function
settings
Pump.
Actual Status; Jumpline for Pump Function
settings
Pre heating
Actual Status; Jumpline for PreHtg Function
settings
Frost monitor
Actual Status of Htg frost protect monitor
Main Index > Unit > Temp control > Heating > Htg frost protect
Parameter
Function
Controller
Output from loop controller; Jumpline to
settings
Setpoint
Frost Setpoint if Unit is On
Standby setpoint
Frost Setpoint if Unit is Off
Main Index > Unit > Temp control > Heating > Heating pump
Parameter
Function
Command
Heating status
Fdbk
Heating pump Feedback
Alarm
Heating pump alarm
Start up delay fdbk
After this Time the Feedback has to be
TRUE
Off by fdbk alarm
In case of a Feedback alarm the Pump is
switched Off
Min run time
Mnimum On Time after a Start
Pump start outs tmp
If Outside Temperature is lower this Value
the Pump Start
Kick date / time
Pump Kick Date and Time
Kick interval
Intervall Time for Pump Kick
Kick on time
Pulse for Pump Kick
Siemens
Building Technologies
17.15.11
Heat recovery > Frost protection
17.15.12
Heat recovery > Frost protect press
17.15.13
Heating
17.15.14
Heating > Frost protection
17.15.15
Heating > Pump
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
HMI
Value range
Unit
0...100
%
-64...64
°C
Value range
Unit
0...100
%
0...5000
Pa
0...5000
Pa
Value range
Unit
0...100
%
%
0...100
%
On...Off
Passive...Active
OK...Frost
Value range
Unit
0...100
%
-64...64
°C
-64...64
°C
Value range
Unit
On...Off
Nofdbk...fdbk
Ok...alarm
0...36000
--- S ---
No...Yes
0...36000
-64...64
°C
0.0...36000.0
h
0...36000
--- S ---
Standard
R S Link
100
X
Section:
5.7.4
3.0
6
Standard
R S Link
100
X
Section:
100
6
5.7.4
200
6
Standard
R S Link
X
X
X
Section:
X
5.8.1
X
X
Standard
R S Link
100
X
Section:
12.0
6
5.8.4
20.0
6
Standard
R S Link
X
X
X
30
6
Section:
Yes
6
5.8.2
180
6
12.0
6
6
Section:
168.0
6
5.8.3
60
6
201 / 244
CE1P3977en_02
Page 201