Siemens Climatix Series Basis Document page 200

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Temp control > Min/max ctrlr sply
Parameter
Function
Min controller
Actual Value Minimum Controller; Jumpline
to settings
Max controller
Actual Value Maximum Controller; Jumpline
to settings
Min setpoint
Setpoint for the min Controller
Max setpoint
Setpoint for the max Controller
Main Index > Unit > Temp control > Hrec damper
Parameter
Function
Controller
Heat Recovery Damper Controller; Jumpline
to settings
Output signal
Heat Recovery Damper Position; Jumpline
to settings
Recovery value
Heat Recovery Value
Min fresh air
Min Open of Heat Recovery Damper
Start up time
Start up Time for Heat Recovery Damper
Start up tmp
Start Up Temperature for Heat Recovery
Damper
Main Index > Unit > Temp control > Heat recovery
Parameter
Function
Controller
Heat Recovery Controller
Output signal
Heat Recovery Position
Command
Heat Recovery status
Pump / cmd
Pump Status; Jumpline for settings
Aalarm
Heat Recovery alarm
Frost monitor
Heat Recovery Frost monitor
Frost protection
Jumpline for Frost protection settings
Frost protect press
Jumpline for settings
Efficiency
Heat Recovery Efficiency
Start up time
For this Time the Hrec run with 100% at
Startup
Start up tmp
If the Outside temperature is lower or equal
this Value the Hrec do run for Start up time
Max speed defrost
Maximum allowed speed in case of Frost
(monitor = Frost)
Main Index > Unit > Temp control > Heat recovery > Pump / cmd
Parameter
Function
Command
Heat Recovery status
Fdbk
Heat Recovery Pump Feedback
Alarm
Heat Recovery Pump alarm
Start up delay fdbk
After this Time the Feedback has to be
TRUE
Off by fdbk alarm
In case of a Feedback alarm the Pump is
switched Off
Min run time
Mnimum On Time after a Start
Kick date / time
Pump Kick Date and Time
Kick interval
Intervall Time for Pump Kick
Kick on time
Pulse length for Pump Kick
200 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 200
BDCX.100820.01GB
Building Technologies
17.15.7 Min/max ctrlr sply
17.15.8 Hrec damper
17.15.9 Heat recovery
17.15.10
Heat recovery > Hrec (pump) cmd
Standard application AHU
HMI
Value range
Unit
0...100
%
0...100
%
15...26
°C
17...50
°C
Value range
Unit
0...100
%
0...100
%
0...100
%
0...100
%
0...600
--- S ---
-64...64
°C
Value range
Unit
0...100
%
0...100
%
On...Off
On...Off
OK...alarm
OK...Frost
0...100
%
0...100
%
0...600
--- S ---
-64...64
°C
0...100
%
Value range
Unit
On...Off
Nofdbk...fdbk
Ok...alarm
0...36000
No...Yes
0...36000
0.0...36000.0
h
0...36000
--- S ---
Standard
R S Link
X
X
Section:
5.5.5
17.0
6
27.0
6
Standard
R S Link
X
X
Section:
0.0
6
5.6
20
6
60
6
15.0
6
Standard
R S Link
X
X
X
X
X
Section:
6
5.7.1
X
X
60
6
15.0
6
20
6
Standard
R S Link
X
X
X
Section:
6
5.7.2
Yes
6
180
6
6
Section:
168.0
6
5.7.3
60
6
CE1P3977en_02
01.02.2010