Siemens Climatix Series Basis Document page 63

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Prerequisites
Function
Parameterization
Parameter
Alarm
Min limit
Maximum deviation
Start up delay
Note
Prerequisites
Function
Parameterization
Parameter
Min controller
Max controller
Min setpoint
Siemens
Building Technologies
5.5.4
Temperatur deviation alarms
– For supply air deviation alarm, a supply air sensor must be available:
Main Index > Configuration > Configuration 1 > Supply tmp sensor = Yes.
– Deviation alarm tmp must be enabled:
Main Index > Configuration > Configuration 2 > Deviation alarm tmp<> No
– For room air deviation alarm, a room or return air sensor must be available:
Main Index > Configuration > Configuration 1 > Room tmp Sensor = Yes.
Setpoint/actual value monitoring of temperature: An alarm is triggered for the fol-
lowing cases when the temperature deviates from the setpoint during a certain pe-
riod:
– Actual value < Min limit.
– Actual value > Setpoint + maximum.
– Actual value < Setpoint – maximum.
– When setpoint – maximum < Min limit, min limit applies as the comparison value.
Main Index > Unit > Temp control > Tmp setpoints > Sply tmp dev alarm
Main Index > Unit > Temp control > Tmp setpoints > Room tmp dev alarm
Range
18. Passive
19. Active
0...99.0 [°C]
0...99.0 [°C]
0...36000 [s]
Monitoring is switched off when the temperature sensor fails.
5.5.5
Supply Minimum Maximum Controller
– Main Index > Configuration > Configuration 1 > Tmp control mode = Room oder
Exhaust
– Main Index > Configuration > Configuration 1 > Supply tmp sensor = Yes
Limits the supply air temperature for pure room or return air control to prevent dis-
charge temperatures that are too high or too low.
Main Index > Unit > Temp control > Min/max ctrlr sply
Range
0...100 [%]
0...100 [%]
15...Max setpoint [°C]
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Functions
Function
Alarm state. Go to settings page for digital alarms. Set all
control-related settings such as alarm delay (default 3600
s).
An alarm is triggered below this temperature.
Maximum allowable deviation between setpoint and actual
value.
The function is activated after this period after a start.
Function
Present value for the minimum limit controller. Go to con-
troller settings page. This is where you enter all control-
related settings.
Present value for the maximum limit controller. Go to con-
troller settings page. This is where you enter all control-
related settings.
Lowest allowable supply air temperature for pure room
temperature or return air temperature control. A controlled
limiting of the cooling setpoint controller occurs for supply
63 / 244
CE1P3977en_02
Page 63
01.02.2010