Siemens Climatix Series Basis Document page 196

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Fan Control > Supply Fan > Setpoints/Settings
Parameter
Function
Stage 2
Output for Stage 2 if Fan control mode is
FixedSpeed, Pressure, Flow or ExhaustSlv
Stage 3
Output for Stage 3 if Fan control mode is
FixedSpeed, Pressure, Flow or ExhaustSlv
Max forcing
Maximum allowed Setpoint for
compensations
Min run time
Min Run Time
Switch on delay
Switch On delay time
Start up delay fdbk
Supply Fan Feedback Start up Delay
Deviation alarm
Actual Status; Jumpline for Settings
Main Index > Unit > Fan Control > Supply Fan > Setpoints/Settings > Deviation alarm
Parameter
Function
Alarm
Actual Status Supply Deviation alarm
Min limit
Lowest allowed Present Value for alarm
Maximum deviation
In maximum allowed Deviation
Start up delay
Delay until the Deviation is supervised
Main Index > Unit > Fan Control > Exhaust fan
Parameter
Function
Actual value
Exhaust fan Actual Value
Controller
Actual Value Controller; Jumpline to settings 0...100
Output signal
Actual Output Signal; Jumpline to settings
Command
Actual Stage; Jumpline to settings
Feedback
Feed back of Supply Fan
Alarm
Exhaust fan alarm
Alarm
Fan alarm if combined Fan
Setpoints/Settings
Actual Value; Jumpline to Exhaust fan
Setpoints and settings
Main Index > Unit > Fan Control > Exhaust fan > Setpoints/Settings
Parameter
Function
Actual step
Exhaust fan Actual Stage
Act supply stpt
Actual Setpoint
Stage 1
Output for Stage 1 if Fan control mode is
FixedSpeed, if Fan control mode is Pressure,
Flow or SupplySlv Setpoint Stage 1
Stage 2
Output for Stage 2 if Fan control mode is
FixedSpeed, if Fan control mode is Pressure,
Flow or SupplySlv Setpoint Stage 2
Stage 3
Output for Stage 3 if Fan control mode is
FixedSpeed, if Fan control mode is
Pressure, Flow or SupplySlv Setpoint Stage
3
Max forcing
Maximum allowed Setpoint for
compensations
Min run time
Min Run Time
Start up delay fdbk
Actual Status; Jumpline for Settings
Deviation alarm
Actual Status; Jumpline for Settings
196 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 196
BDCX.100820.01GB
Building Technologies
17.14.4 Supply fan deviation alarm
17.14.5 Exhaust fan
17.14.6 Exhaust fan settings
Standard application AHU
HMI
Value range
Unit
0...100
%
l/s
Pa
0...100
%
l/s
Pa
0...19900
%
l/s
Pa
0...36000
--- S ---
0...36000
--- S ---
0...36000
--- S ---
Passive
Active
Value range
Unit
Active...passive
-64...64
°C
-64...64
°C
0...36000
--- S ---
Value range
Unit
0...100
%
%
0...100
%
Off...St3
Nofdbk...fdbk
OK...alarm
OK...alarm
Value range
Unit
Off...St3
0...100
%
0...100
%
l/s
Pa
0...100
%
l/s
Pa
0...100
%
l/s
Pa
0...19900
%
l/s
Pa
0...36000
--- S ---
Passive
Active
Passive
Active
Standard
R S Link
80%
6
100%
6
Section:
5.4.3
0%
6
0
6
30
6
60
6
x
Standard
R S Link
X
10
6
Section:
10
6
5.4.5
60
6
Standard
R S Link
X
X
X
X
Section:
6
5.4.3
6
6
6
Standard
R S Link
X
X
40%
6
80%
6
Section:
5.4.3
100%
6
0%
6
0
6
x
x
CE1P3977en_02