15.3.2 Temperatures
The listed hard assignments are possible for all temperature sensors.
Pos
NUsd, Comm, X1...X8, X11...X18,
X21...X28
• Supply air
• Room
• Room 2
• Exhaust air
• Outside air
• Heating frost
• Extract air
• Heat recovery water
• Hrec supply air
• Supply air 2 (extra supply air temperature, if heating 2 or Cooling 2 to us
comming.
• Heating 2 frost
• Auxiliary (additional connectable temperature)
Position
Explanation
X1...X8
Terminal on basis controller.
X11...X18
Terminal on extension module 1.
X21...X28
Terminal on extension module 2.
Comm
Sensor is connected via communication and therefore does not oc-
cupy a hardware input. Some sensors can also be connected via
communication (see lists in the documentation on the basics for
LON, ModBus, BacNet).
Sensors may also be enabled in parallel as well (via hardware and
communication).
The value selector must be set accordingly when enabling via com-
munication (for details page on Analog Inputs, Sec. 6.5.2.).
NUsd
No used: The hardware position is not yet selected. The plant is
locked against switching on if an enabled sensor is set to NUsd and
the following fault issued: NotConfigured (Function enabled, but
hardware not assigned).
The following sensor types are possible for all temperature sensors.
• Pt1k: Platin 1000 Ohm
• Ni1k: Nickel 1000 Ohm
• NTC10K: NTC 10 kOhm
• Ni1kLG: Nickel 1000 Ohm LG (SBT)
15.3.3 Pressures / flows
The listed hard assignments are possible for all pressure and flow sensors.
Pos
NUsd...X28
NUsd...X28
NUsd...X28
NUsd...X28
NUsd...X28
Standard application AHU
Configuration
Type
Pt1k, Ni1k, Ni1kLG, NTC10K
Fact (K-Faktor)
Scale (x Pa bei 10 V)
---
0...5000
---
0...5000
0.00...99.90
0...5000
0.00...99.90
0...5000
---
0...5000
CE1P3977en_02
01.02.2010