Siemens Climatix Series Basis Document page 160

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Parameter
Fan steps freq conv
Flow display
Fan steps type
Fan alarm
Fan fdbk
Fan deviation alm
160 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 160
BDCX.100820.01GB
Building Technologies
Range
Function
Activation of additional digital outputs depending on the selected fan
type.
1Step
Digital output to enable variable speed drive (always enabled).
2Steps
An additional digital output for optional wiring depending on fan step 2.
3Steps
Two additional digital outputs for optional wiring depending on fan step
3.
Display flow and possible output.
No
Function not available.
Yes
Display of supply air and (if enabled) exhaust air flow. Analog inputs
are enabled if not already enabled by the fan control setting.
Required output for fan control relating to settings for fan control
mode, TSP steps and fan steps freq conv.
Separated
Digital output for each step.
Example:
Fan control mode = direct / TSP steps = 2 / Exhaust fan = Yes
---> 4 digital outputs: Step 1 and Step 2 each, separated for supply air
and exhaust air fans.
SepCombine
Separate outputs on the first step, common outputs for additional
steps.
Example:
Fan control mode = pressure / TSP function = Step+tmp / TSP steps =
3 /
Exhaust fan = Yes / Fan steps freq conv = 3.
---> 4 digital outputs: Step 1 each as separate variable speed drive
enable, two additional outputs open for use (Fan steps freq conv) for
Step2 and Step 3.
Binary
Outputs for the steps are binary coded. The setting is permitted for fan
control mode = direct or directVar.
Example:
Fan control mode = direct / TSP function = Step+tmp / TSP steps = 3 /
Exhaust fan = Yes
---> 4 digital outputs: 2 digital output each per fan (Step1 = DO1
TRUE; Step 2 = DO2 TRUE; Step3 = DO1 und DO2 TRUE).
Inputs for fan alarms (e.g. thermal contact). Logical 1 = alarm.
No
No alarm.
Combined
Digital input for common alarm.
Supply
Digital input for supply air fan alarm.
Exhaust
Digital input for exhaust air fan alarm.
Sply+Exh
Two digital inputs for alarms from supply and exhaust air fans.
Inputs for operating message from the fans (e.g. pressure switch or
relay contact). Logical 1 = Fan running.
No
No feedback.
Combined
Digital input for common operating message.
Supply
Digital input for supply air fan operating message.
Exhaust
Digital input for exhaust air fan operating message.
Sply+Exh
Two digital inputs for operating messages from supply and exhaust air
fans.
Setpoint/actual value monitoring of the pressure or flow. An alarm is
triggered for deviation over a set period.
No
No monitoring.
Supply
Supply air monitoring only.
Exhaust
Exhaust air monitoring only.
Sply+Exh
Supply and exhaust air monitoring.
Standard application AHU
Configuration
CE1P3977en_02
01.02.2010