Quick Start Parameters

Alter the Quick Start Parameters as required to suit installation requirements.
If the Quick Start Guide was used, proceed to Application Parameters.
Technical Reference
Refer to
P001
OPERATION
Enter the type of RUN mode operation desired.
Select: "level", to display how full the vessel is (from Empty P006) .
values: 0 = out-of-service
P002
MATERIAL
Enter the type of material to be monitored.
If the material presents a flat surface perpendicular to the transducer beam,
select liquid.
values: 1 = liquid or flat surface (preset)
7ML19985AN02
Application Examples for assistance, if required.
"space", to display how empty the vessel is (from Span P007).
"distance", to display material surface distance from the transducer
face.
When "out-of-service" is selected, the transducer is removed from the
RUN mode scan sequence and all Peripherals hold "last known" values/
operating status for the Point Number displayed.
1 = level
2 = space
3 = distance (preset)
2 = solid
SITRANS LU10 – INSTRUCTION MANUAL