Parameter
Hum control unit
Hum stpt selection
Dehum tmp prio
Dew point control
Hum deviation
alarm
Humidifier pump
Hum pump alarm
Humidifier fdbk
Cooling pump
Cooling pump
alarm
164 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 164
BDCX.100820.01GB
Building Technologies
Range
Function
Type of humidity control.
Relative
Relative humidity control.
Absolute
Absolute humidity control.
CascRelAbs
Cascade control with relative room and absolute supply air humidity
control.
Predefined variants for humidity setpoints.
Hum/dehum
Humidification and dehumidification setpoint is entered directly.
+/- HalfDz
Base setpoint and dead zone is entered:
Humidity setpoint = Base setpoint – half dead zone.
Dehumidification setpoint = Base setpoint – half dead zone.
Hum+Dz
Humidification setpoint and dead zone is entered:
Dehumidification setpoint = Humidification setpoint + dead zone.
dehum-Dz
Dehumidification setpoint and dead zone is entered:
Humidification setpoint = Dehumidification setpoint – dead zone.
Dehumidification is reduced dependent on the heating output.
No
Function not enabled.
Yes
As of 90%, heating valve position reduces dehumidification.
No
Dew point monitoring. Minimum limitation to supply air temperature
Yes
relating to dew point control.
Monitors setpoint/actual value of humidification. An alarm is triggered
for deviations over a certain period.
No
No monitoring.
Room/Exh
Monitors room humidity only.
Supply
Monitors supply air humidity only.
Sply+RmExh
Monitors supply air and room humidity.
No
No humidifying pump.
Yes
Humidifying pump without pump kick. Digital output for the pump.
Yes+Kick
Humidifying pump with pump kick. A digital output for pump and acti-
vation of pump kick.
Pump kick: Pump is switched on for a short period after idling for a
longer period. This prevents lock up.
No
Pump without alarm or feedback.
Alarm
Pump with alarm. Digital input for pump alarm. Logical 1 = alarm, im-
mediately shuts down the pump.
Fdbk
Pump with feedback. Digital input for feedback (logical 1 = Pump run-
ning).
Both
Pump with alarm and feedback. Two digital inputs for pump alarm and
feedback.
No
Humidifier without feedback.
Yes
Humidifier with feedback: Digital input for feedback is enabled (logical
1 = Humidifier running).
No
No water cooling pump.
Yes
Water cooling pump without pump kick. Digital output for the pump.
Yes+Kick
Water cooling pump with pump kick. A digital output for pump and ac-
tivation of pump kick.
Pump kick: Pump is switched on for a short period after idling for a
longer period. This prevents lock up.
No
Pump without alarm or feedback.
Alarm
Pump with alarm. Digital input for pump alarm. Logical 1 = alarm, im-
mediately shuts down the pump.
Fdbk
Pump with feedback. Digital input for feedback (logical 1 = Pump run-
ning).
Standard application AHU
Configuration
CE1P3977en_02
01.02.2010