Siemens Climatix Series Basis Document page 62

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Prerequisites
Function
Setpoint compensation
during summer
Setpoint compensation
during the winter.
Parameterization
Parameter
Outs air tmp start
Outs air tmp end
Delta
Note
62 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 62
BDCX.100820.01GB
Building Technologies
5.5.3
Summer/Winter compensation
– Summer/winter compensation must be enabled:
Main Index > Configuration > Configuration 2 > So-Wi comp tmp = Yes
– An outside air temperature sensor must be available:
Main Index > Configuration > Configuration 1 > Outside tmp sensor <> No.
• Summer compensation: Adjustment to temperature setpoint (depending on
control, supply air, room or return air) relevant to control when the outside air
temperature is high during the summer.
• Winter compensation: Adjustment to temperature setpoint (depending on con-
trol, supply air, room or return air) relevant to control when the outside air tem-
perature is low during the winter.
Main Index > Unit > Temp control > Setpoints > Summer comp
Main Index > Unit > Temp control > Setpoints > Winter comp
Range
-64.0...64.0 [°C]
-64.0...64.0 [°C]
-64.0...64.0 [K]
Setpoint compensation is not undertaken during the summer and winter when the
outside air temperature sensor fails.
Standard application AHU
Functions
Function
Outside air temperature at which point the compensation
begins to act.
Outside air temperature by which the maximum (summer)
or minimum setpoint is reached.
Maximum setpoint temperature-compensation.
CE1P3977en_02
01.02.2010