Siemens Climatix Series Basis Document page 169

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Terminal positions
HW IO
Supply
Room
Outside
Terminal positions
HW IO
External control 1
External control 2
Siemens
Building Technologies
Position
Explanation
X1...X8
Terminal on basis controller.
X11...X18
Terminal on extension module 1.
X21...X28
Terminal on extension module 2.
Comm
Sensor is connected via communication and therefore does not oc-
cupy a hardware input. Some sensors can also be connected via
communication (see lists in the documentation on the basics for
LON, ModBus, BacNet).
Sensors may also be enabled in parallel as well (via hardware and
communication).
The value selector must be set accordingly when enabling via com-
munication (for details page on Analog Inputs, Sec. 6.5.2.).
NUsd
No used: The hardware position is not yet selected. The plant is
locked against switching on if an enabled sensor is set to NUsd and
the following fault issued: NotConfigured (Function enabled, but
hardware not assigned).
15.3.4 Humidity
The listed hard assignments are possible for all humidity sensors.
Pos
NUsd,Comm,X1...X28
NUsd,Comm,X1...X28
NUsd,Comm,X1...X28
Position
Explanation
X1...X8
Terminal on basis controller.
X11...X18
Terminal on extension module 1.
X21...X28
Terminal on extension module 2.
Comm
Sensor is connected via communication and therefore does not oc-
cupy a hardware input. Some sensors can also be connected via
communication (see lists in the documentation on the basics for
LON, ModBus, BacNet).
Sensors may also be enabled in parallel as well (via hardware and
communication).
The value selector must be set accordingly when enabling via com-
munication (for details page on Analog Inputs, Sec. 6.5.2.).
NUsd
No used: The hardware position is not yet selected. The plant is
locked against switching on if an enabled sensor is set to NUsd and
the following fault issued: NotConfigured (Function enabled, but
hardware not assigned).
15.3.5 Digital inputs
The listed hard assignments are possible for all digital inputs.
Pos
NUsd,Comm,X4...X28,DI1...DI5
NUsd,Comm,X4...X28,DI1...DI5
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Configuration
Y1 (Feuchte bei 0 V
Y2 (Feuchte bei 10 V)
0.0...100.0 %r
0.0...100.0%r
0.0...100.0 %r
0.0...100.0%r
0.0...100.0 %r
0.0...100.0%r
169 / 244
CE1P3977en_02
Page 169