Detail Pages: Analog Outputs - Siemens Climatix Series Basis Document

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Outputs > Analog outputs > Element
Parameter
Function
Manual operation
Enter the value. Function enabled by enter-
ing a value.
Manual operation
Status and reset after NULL.
NULL: Auto; The program controls the out-
put.
Active: A value entered in the upper line.
Present Value
Present value for output.
Reliability
Reliability state for hardware.
Active prio
Displays the wired Prio elements currently
on the output.
Special settings
Go to special settings page.
Special infos
Go to special info page.
Priority array
Go to priority array page.
Main Index > Unit > Outputs > Analog outputs > Element > Special settings
Parameter
Function
Msg class fault
Set alarm class (and groups A, B, C):
Set the Unit in Stop Mode
Set the Unit in Off Mode
Only Message
Only Message
No Message, no Alarm
High limit
Upper limit of output signal.
Low limit
Lower limit of output signal.
Main Index > Unit > Outputs > Analog outputs > Element > Special infos
Parameter
Function
Physical value
Value on output. Only differs from present
value with out of service intervention via
BACnet. OK?
Disable OffNormal
Check: The output is disabled by an alarm.
MMI-Texte so OK?
Example: Value greater than high limit
value:
Output OK.
Output switched off.
ToOffNormal
Date and time the last off normal alarm
occurred.
ToFault
Data and time last fault alarm (Reliability <>
0) occurred.
ToNormal
Date and time last alarm was reset.
Communication infos Not enabled for analog outputs.
214 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 214
BDCX.100820.01GB
Building Technologies
18.2

Detail pages: Analog outputs

18.2.1 General
18.2.2 Special settings
18.2.3 Special information
Standard application AHU
Time scheduler
Value range
Unit
0...100
[%]
NULL
Active
0...100
[%]
OK.
Other
Process error
Config err
Out of serv.
Prio1
....
Prio16
Default
Value range
Unit
Danger (A)
High (A)
Low (B)
Warning (C)
No alarm
0...100
[%]
0...100
[%]
Value range
Unit
0...100
[%]
Passive
Active
Day of week,
dd.mm.yyyy hh:mm:ss
Day of week,
dd.mm.yyyy hh:mm:ss
Day of week,
dd.mm.yyyy hh:mm:ss
Standard R S Link
6
4
6
4
Section:
6.2.1
6
4
4
6
6
Standard R S Link
4
4
Section:
6.2.2
4
4
4
4
Standard R S Link
4
4
Section:
6.3.3
4
4
4
4
CE1P3977en_02
01.02.2010