Detail Pages: Digital Outputs - Siemens Climatix Series Basis Document

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Outputs > Analog outputs > Element > Priority array
Parameter
Function
Default
Replacement value, when no priority is
active.
Prio 01
Value for priority 1.
...
...
Priority 16
Value for priority 16.
Main Index > Unit > Outputs > Digital outputs > Element
Parameter
Function
Manual operation
Manual operation on element (e.g. pump).
Off.
On.
Auto: The program controls the output.
Present Value
Present value for output.
Reliability
Reliability state for hardware.
Active prio
Displays the wired Prio elements currently
on the output.
Operating hours
Number of operating hours for the output.
Operating seconds
Number of operating seconds for the out-
(Reset)
put. Enter 0 seconds to reset operating
hours to 0.
Last op hours reset
Date and time for the last time operating
hours was reset.
Special settings
Go to special settings page.
Special infos
Go to special info page.
Priority array
Go to priority array page.
Main Index > Unit > Outputs > Digital outputs > Element > Special settings
Parameter
Function
Contact Function
Changes output from Normal open to Nor-
mal closed:
Normal open
Normal closed (In this position, the output is
enabled when the plant is shut down).
Main Index > Unit > Outputs > Digital outputs > Element > Special infos
Parameter
Function
Physical value
Value on output. Only differs from present
value with out of service intervention via
BACnet. OK?
Disable OffNormal
Display OffNormal alarms.
No alarm pending.
Alarm pending.
BACnet fdbk value
If connected: Feedback value from the bus.
Communication infos Not enabled for digital outputs.
Siemens
Building Technologies
18.2.4 Priority array
18.3

Detail pages: Digital outputs

18.3.1 General
18.3.2 Special settings
18.3.3 Special information
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Time scheduler
Value range
Unit
0...100
[%]
0...100
[%]
...
0...100
[%]
Value range
Unit
Off
On
NULL
Off
[%]
On
OK.
Other
Process error
Config err
Out of serv.
Prio1
....
Prio16
Default
0...
[h]
0...
[s]
Wday, dd.mm.yyy
hh:mm:ss
Value range
Unit
NO
NC
Value range
Unit
Off
On
Passive
Activ
Standard R S Link
4
X
4
X
Section:
4
X
6.2.4
4
X
Standard R S Link
4
4
6
4
6
4
6
4
Section:
6.3.1
6
6
6
4
6
6
Standard R S Link
4
4
NO
Section:
6.3.2
Standard R S Link
6
6
Section:
6.3.3
6
6
215 / 244
CE1P3977en_02
01.02.2010
Page 215