Parameter
Outs air tmp X2
Output signal Y1
Output signal Y2
Pre htg on time
Min off time
Prerequisite
Enable electric register
Parameter
Electrical heating /
El Heating 2
Configuration
Parameter
El Htg alarm /
El heating 2 alarm
El heating 2 control
Function
Note
Stage control
Siemens
Building Technologies
Range
0.0...50.0 [°C]
0...100 [%]
0...100 [%]
0...600 [s]
0.0...1400.0 [min]
5.9

Electrical heating / Electrical heating 2

5.9.1
General
Electrical heating / Electrical heating 2 are enabled and preconfigured in configura-
tion 1, configuration 2 and configuration I/Os.
Main Index > Configuration > Configuration 1
Range
– No
– Analog
– 1Step
– 2Steps
– 3Steps
Main Index > Configuration > Configuration 2
Range
– No
– Alarm
– StandAlone
– InSequence
Both electric registers can be deployed with up to 3 stages (binary). An alarm is
possible for each register. Register output is limited by fan out, which prevent the
register from overheating. The additional electric heating register can be operated
as a separate register with its own setpoint.
The electrical heating register is forced off if:
– Night unoccupied (temperaturstart) cool
– Summer night cooling
A maximum of one of the two additional registers Heating 2 or El heating 2 can be
integrated into the temperature control sequence.
The stages are controlled as follows for electric heating registers:
DO1
DO2
Off
0
0
Stage1
1
0
Stage2
0
1
Stage3
1
1
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Functions
Upper design temperature.
Value for lower design temperature.
Value for upper design temperature.
Time to preheat lines and register.
Minimum off time for the function after preheating is
completed.
Function
– No (additional) electric register.
– (Additional) electric register with analog con-
trol.
(Additional) single-stage electric heating register.
(Additional) two-stage electric heating register.
(Additional) three-stage electric heating register.
Function
– No alarm.
– With alarm.
– Not integrated in sequence.
– Integrated in sequence.