Task
Distribution to basis con-
troller and extension
modules.
Note
Prerequisite
Start
Parameter
Range
Temperatures
Pressures / flows
Humidity
Digital inputs
Digital alarms
Other
Outputs damper
Output fans
Outputs tmp control
Outputs humidifier
Outputs auxiliary
Outputs alarm
Configuration IOs
NotDone
Done
Reset Required !!
Passive
Execute
Siemens
Building Technologies
15.3

Configuration I/Os

15.3.1 Start page
In Configuration I/Os, the required I/Os, previously set in Configuration 1 and Con-
figuration 2 by the selected functions, are assigned to hardware.
Moreover, the parameterization of the required conversion for the sensors takes
place here (e.g. Ni1000; Pt1000; 0-10 V = 0-1000 Pa).
• Basis controller: All single-digit positions, e.g. X1.
• Extension module 1: All positions X1x, DI1x, DO1x, AO1x, e.g. X11, DO14.
• Extension module 2: All positions X1x, DI1x, DO1x, AO1x, i.e., for example,
X11, DO14.
The I/Os on the extension modules are available, if the module was enabled in
Configuration 1.
Configuration 1 and Configuration 2 completed with one reset each.
As required:
Start page > Password Enter
then:
Main Index > Configuration > Configuration IO's
Function
Go to hardware configuration page for all temperature sensors.
Go to hardware configuration page for all pressure and flow sensors.
Go to hardware configuration page for all humidity sensors.
Go to hardware configuration page for all digital inputs without alarm
function.
Go to hardware configuration page for all digital inputs with alarm
function.
Go to hardware configuration page for air quality sensor and the ex-
ternal setpoint adjuster.
Go to hardware configuration page for supply, exhaust air and fire
dampers.
Go to hardware configuration page for fans.
Go to hardware configuration page for heating, cooling heat recovery,
etc.
Go to hardware configuration page for the humidifier.
Go to hardware configuration page for auxiliary functions.
Go to hardware configuration page for both alarm outputs.
This parameters enable the plant after successful parameterization.
Enable occurs when Configuration 1, Configuration 2 and Configura-
tion I/Os are completed, i.e. when each has the value "done".
Plant locked against switching on.
The plant is unlocked after complete parameterization, i.e. it can be
switched on.
Reset required after successful parameterization in Configuration
I/Os. Assumes the appropriate presettings for Configuration I/Os.
After reset, value automatically goes from execute to passive.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Configuration
167 / 244
CE1P3977en_02
Page 167
01.02.2010