Siemens Climatix Series Basis Document page 120

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Parameter
Settings
Inputs
Reset required !!
MODBUS configuration
Parameter
Communication
Internal
Internal Slave address
Internal settings
RS485
TCP/IP
Module1 Modbus
Module1 Modbus
Module1 Modbus
RS485 MODBUS
parameterization
Parameter
Baud rate
Parity
Stop bit
Delay time
Parameter
Response timeout
Termination
120 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 120
BDCX.100820.01GB
Building Technologies
Range
− 2 RU
− 
− Execute
Unit > System overview > Communication > Modbus
Range
− OK
− Alarm
− Disable
− Master
− Slave
0...247
Unit > System overview > Communication > Modbus > RS485
Range
− 2400
− 4800
− 9600
− 19200
− 38400
− Even
− Odd
− None
− One
− Two
0...2147483647 [ms]
Range
0...2147483647 [ms]
− Passive
Standard application AHU
Communication
Function
ing 1 RU, 1snsr+RU or 2 RU, the interface to the
room unit connection is enabled.
Goes to page with all settings relevant to param-
eterizing room units.
Go to page with temperature inputs.
As a matter of principle, the controller must be
set after parameterization to assume the data.
Function
Status of Modbus communication.
Generally enables internal MODBUS and func-
tion of MODBUS over RS485:
− Internal interface is disabled.
− Internal RS485 interface is master.
− Internal RS485 interface is slave.
Controller address on the RS485 bus.
Go to parameter page for RS485 MODBUS in-
terface.
Go to parameter page for TCP/IP settings.
Go to parameter page for MODBUS interface on
module 1.
Go to parameter page for MODBUS interface on
module 1.
− Go to parameterization page for MODBUS
interface on module 1.
Function
Transmission rate on bus. All participants must
have the same setting.
Parity. All participants must have the same set-
ting.
Number of stop bits. All participants must have
the same setting.
Response telegram delay.
Function
Settings access time for master.
The master must undertake read access within this
period, otherwise an alarm is triggered (this func-
tion is not yet fully implemented).
Internal bus connection for the basis controller:
− No bus terminating resistor.