Prerequisite
Enable
Parameter
TSP steps
Fan control mode
Configuration
Parameter
Fan steps freq conv
50 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 50
BDCX.100820.01GB
Building Technologies
5.4

Fan control

This section deals with the topics fans, air flows, air pressures and associated con-
trol, such as pressure control.
5.4.1
Configuration
The main air control functions are enabled, preconfigured and the inputs/outputs
are defined in confuration1 and configuration 2 and Configuration I/Os. Exhaustfan
should be set to "combined" if combined outputs for the supply fan and exhaust are
wanted, and set to "no" if no exhaust fan.
Main Index > Configuration > Configuration 1
Range
Function
Enable possible fan steps.
– 1Step
– Single-step fan (only one setpoint).
– 2Steps
– 2-step fan (two setpoints).
– 3Steps
– 3-step fan (three setpoints).
Select fan and control type.
– Direct
– Digitally controlled stepped fans.
– DirectVar
– Digitally controlled variable speed drives.
– FixedSpeed
– Stepped analog controlled variable speed drive with digital re-
lease [%].
– Pressure
– Pressure-controlled plant with modulating controlled variable
speed drive and digital release [Pa].
– Flow
– Volume-controlled plant with modulating controlled variable
speed drive and digital release [l/s].
– SupplySlv
– One digital and analog output each for the variable speed drives
in pressure-controlled plants where the supply air fan operates
dependent on the exhaust fan [Pa]/[l/s]. The exhaust fan is
pressure controlled and the exhaust flow is calculated, the
supply fan is flow controlled to follow the exhaust flow.
– One digital and analog output each for the variable speed drives
– ExhaustSlv
in pressure-controlled plants where the exhaust air fan operates
dependent on the supply air fan [Pa]/[l/s]. The supply fan is
pressure controlled and the supply flow is calculated, the
exhaust fan is flow controlled to follow the supply flow.
Main Index > Configuration > Configuration 2
Range
Function
Activation of additional digital outputs depending on the selected
fan type. Function available only for analog controlled variable
speed drives (Fan control mode <> Direct or DirectVar). The switch
does not affect air control and fan behavior.
– 1Step
– Enable variable speed drive (always active).
– 2Steps
– Output for optional wiring depending on fan step 2.
– Outputs for optional wiring depending on fan step 3.
– 3Steps
Standard application AHU
Functions
CE1P3977en_02
01.02.2010