Parameter
Alarm
Start up delay fdbk
Off by fdbk alarm
Outs tmp start
Min run time
Note
Prerequisite
Function
Parameter
Parameter
Kick date / time
Kick interval
Kick on time
Note
Siemens
Building Technologies
Range
– OK
– Alarm
0...36000 [s]
– No
– Yes
-64...64 [°C]
0...36000 [s]
Feedback can only be used as alarm, when Contact function = NO (Normally
Open) and the element is set to ON.
5.8.3
Pump kick
Pump kick is enabled.
Main Index > Configuration > Configuration 2 > Heating pump = Yes+Kick
Main Index > Configuration > Configuration 2 > Heating 2 pump = Yes+Kick
The pump is switched on for a short period for longer idle periods. This prevents
lock up.
Main Index > Unit > Temp control > Heating > Pump
Main Index > Unit > Temp control > Heating 2 > Pump
Range
Mo 00:00...So 23:29
0.0...36000.0 [h]
0.0...36000 [s]
Kick date/time = * *:* and kick interval = 0 --->
No pump kick is run.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Functions
Function
Current pump alarm state.
Go to page with digital input settings. For exam-
ple, you can set the time for jitter protection (De-
fault: 0 s).
Defines the period after a pump start without
feedback before a feedback alarm is triggered.
Jitter time is enabled exclusively if the feedback
is pending after this period.
Determines, in the event of a feedback fault,
whether a pump command is still pending or
whether to switch off the command.
The pump starts when the outside air tempera-
ture drops below this value. Heat is thus avail-
able immediately for heating (passive frost pro-
tection) when switching on the plant.
The function is disabled when no outside air
temperature is configured or the sensor fails.
Define the minimum runtime for the pump after a
start.
Function
Weekday and time for pump kick. Sets the weekday
(Mon...Sun) and time to run the pump kick. Examples:
Mon *:*
Each Monday at midnight.
Sat 07:* Each Saturday at 7:00 am.
* *:*
Time is not relevant; the kick interval applies
accordingly.
Idle time for pump kick. Set the idle time after which a
pump kick is run. Examples:
168
After 168 hours.
123.4
After 123 hours and 24 minutes.
0
Idle time is not relevant; kick date/time applies
accordingly.
Set the period for the pump kick. Examples:
10
Period = 10 seconds.
0
Period = 1 controller cycle (ca. 150 ms).
75 / 244
CE1P3977en_02
Page 75
01.02.2010