Basis Document Siemens Climatix Control System
Siemens
Page 154
BDCX.100820.01GB
Building Technologies
15.1

Configuration 1

Set superposed settings for the plant in Configuration 1.
– Configuration occurs setting-by-setting, i.e. you cannot bypass any lines.
– Configuration 1 must be completed with reset prior to starting Configuration 2.
As required: Enter password for level 4:
Start page > Password Enter
then:
Main Index > Configuration > Configuration 1
Range
Explanation
No
The basis controller I/Os are enough for configuration.
One
One extension module is connecting using address 1.
DIP switches 5 and 6 must be set to ON on the module.
Two
Two extension modules are connected with addresses 1 and 2.
DIP switch 5 must be set to ON on extension module 1; on exten-
sion module 2, DIP switches 4 and 6.
No
No fire alarm.
alarm
External fire alarm such as smoke detectors, thermostats, fire de-
tection control units, etc.
tmp
Internal fire alarm via temperature measurement of supply and ex-
haust air temperature, when both sensors exist. A fire alarm is trig-
gered when on of the two temperatures breaches a certain value.
alarm+tmp
Both fire alarms.
No
No filter alarm.
Combined
Supply and exhaust filter with common alarm input.
Supply
Supply filter alarm input only.
Exhaust
Exhaust filter alarm input only.
Sply+Exh
Two separate filter alarm inputs for supply and exhaust filters.
No
Input for emergency stop. A TRUE signal at this input immediately
Yes
shuts down the plant. No alarm is triggered.
No
Input to acknowledge/reset an alarm. Alarms still pending are ac-
Yes
knowledged; no longer pending alarms are reset.
No
Input for Summer/Winter changeover: A TRUE signal on this input
Yes
means Summer = Enabled.
No
No time switch program.
Steps
Time switch program with possible settings for fan stages (Off and
Stx). The parameter TSP Steps determines the number of possible
steps x.
Steps+tmp
Time switch program with settings for fan stages and temperature
control mode (Off, Ecox and Comx). The parameter TSP Steps
determines the number of possible stages x.
The temperature mode, comfort or economy have separate set-
points for temperature control.
Enable possible fan steps. This setting influences the number of
setpoints for controlled fans.
1Step
TSP function = Steps ---> Possible time switch program settings:
Off, St1.
TSP function = Steps+tmp ---> Possible time switch program set-
tings: Off, Eco1, Com1.
Standard application AHU
Configuration
CE1P3977en_02
01.02.2010