17.15 Temperature Control - Siemens Climatix Series Basis Document

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Fan Control > Exhaust fan > Setpoints/Settings > Deviation alarm
Parameter
Function
Alarm
Actual Status Exhaust Deviation alarm
Min limit
Lowest allowed Present Value for alarm
Maximum deviation
In maximum allowed Deviation
Start up delay
Delay until the Deviation is supervised
Main Index > Unit > Fan Control > Summer comp
Parameter
Function
Outside tmp start
Start Temperature for Summer
compensation
Outside tmp end
End Temperature for Summer
compensation
Delta
delta for Summer compensation
Main Index > Unit > Fan Control > Winter comp
Parameter
Function
Outside tmp start
Start Temperature for Winter compensation -64...64
Outside tmp end
End Temperature for Winter compensation
Delta
delta for Winter compensation
Main Index > Unit > Fan Control > OpHoursSettings
Parameter
Function
Op hours alarm
Operation hours alarm
Enble ophours alarm Enables this Function, if the Operation
Hours from Supply Fan are > than
Operation Hours Limit => alarm
Op hours limit
Operation hours Limit
Main Index > Unit > Temp control
Parameter
Function
Act controlled tmp
Actual Value of the controlled Temperature
Tmp setpoints
Jumpline to tmp Setpoints
Cascade controller
Actual Heating Setpoint; Actual Cooling
SetpointJumpline to settings for Cascade
Controller
Min/max ctrlr sply
Jumpline to settings for Min Max Controlling
Hrec damper
Actual Value; Jumpline for Heat recovery
Damper settings
Heat recovery
Actual Value; Jumpline for Heat recovery
settings
Heating
Actual Value; Jumpline for Water Heating
settings
Electrical heating
Actual Value; Jumpline for electrical Heating
settings
Cooling
Actual Value; Jumpline for Cooling settings 0...100%
Heating 2
Actual Value;Jumpline for Heating 2 settings 0...100%
Siemens
Building Technologies
17.14.7 Exhaust fan deviation alarm
17.14.8 Fan summer cmp
17.14.9 Fan winter cmp
17.14.10
Fan OpHoursSettings

17.15 Temperature control

17.15.1 Start page
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
HMI
Value range
Unit
Active...passiv
-64...64
°C
-64...64
°C
0...36000
--- S ---
Value range
Unit
-64...64
°C
-64...64
°C
-100...100
%
Value range
Unit
°C
-64...64
°C
-100...100
%
Value range
Unit
Active*Passive
No*Yes
0...999999
h
Value range
Unit
°C
-64.0...64.0
°C
0...100%
%
0...100%
%
0...100%
%
0...100%
%
%
%
Standard
R S Link
X
10
6
Section:
10
6
5.4.5
60
6
Standard
R S Link
25.0
6
30.0
6
Section:
5.4.4
0.0
6
Standard
R S Link
5.0
6
Section:
-20.0
6
5.4.4
0.0
6
Standard
R S Link
Passive
6
No
6
Section:
5.4.6
17520
6
Standard
R S Link
x
6
6
6
6
6
6
Section:
5.5.1
6
6
197 / 244
CE1P3977en_02
Page 197