Siemens SINAMICS G120 Operating Instructions Manual page 374

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.2 Technical data, Power Modules
Property
Storage temperature
Relative humidity
Pollution
Environmental requirements
Shock and vibration
Installation altitude
Permissible short-circuit cur-
rent
Overvoltage category
Standards
If fuse-protected with a listed Class J or 3NE1 fuse, rated voltage 600 VAC with the rated current of the specific inverter.
1)
UL available soon for frame sizes D ... F
2)
374
Version
HO base load power without derating
LO/HO base load power with derating:
Details - (Page 428).
-40 °C ... +70 °C
< 95% - condensation not permissible
Protected according to pollution degree 2 to EN 61800-5-1: 2007
Protected against damaging chemical substances according to environmental class 3C2
to EN 60721-3-3; 1995
Long-term storage in the transport packaging according to Class 1M2 to
EN 60721-3-1: 1997
Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
without derating:
up to 1000 m above sea level
with derating:
up to 4000 m above sea level
Frame size D ... F: 65 kA
Supply circuits:
Non-supply circuits:
UL
, CE, C-tick
1),2)
The drive only satisfies the UL requirements when UL-certified fuses are used.
1)
Overvoltage category III
Overvoltage category II
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
0 °C ... +50 °C
Up to 60° C
For details, see Restrictions for spe-
cial ambient conditions (Page 428)
Converter with CU230P-2 Control Units

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents