Advertisement

Commissioning
5.3 Commissioning using a BOP-2 operator panel
9. Application and control mode
122
9.1.
The selection option depends on the Power Module being used. There is no se-
lection option for PM230 Power Modules.
9.2.
Select the application:
VEC STD
In all applications, which do not fit the other
setting options.
PUMP FAN
Applications involving pumps and fans
SLVC 0HZ
Applications with short ramp-up and ramp-
down times. However, this setting is not suita-
ble for hoisting gear and cranes/lifting gear.
PUMP 0HZ
Setting only for steady-state operation with
slow speed changes. We recommend setting
VEC STD if load surges in operation cannot
be ruled out.
Select the control mode:
VF LIN
U/f control with linear characteristic
VF LIN F
Flux current control (FCC)
VF QUAD
U/f control with square law characteristic
SPD N EN
Vector control without encoder
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB