Siemens SINAMICS G120 Operating Instructions Manual page 299

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p2380
p2381
p2382
p2383
p2384
p2385
p2386
p2387
Note
Technology controller as main setpoint
To use the technology controller as main setpoint for the cascade control, interconnect the
main setpoint with the technology controller output (p2251 = 0, p2200 =1)
For more information, see the parameter descriptions and function diagram 7036 in the List
Manual.
Additional conditions when the hibernation mode is enabled
In order that the cascade control and hibernation mode functions operate without any
conflict, you must parameterize the cascade control so that the following conditions are
satisfied.
● p2392 < p2373
The restart value of the hibernation mode (p2392) must be lower than the activation
threshold for the cascade control (p2373)
● p2373 < p2376
The activation threshold for the cascade control (p2373) must be less than the
overcontrol threshold for the cascade control (p2376).
● It is not permissible that the main drive is in the hibernation mode.
● The actual speed must be higher than the restart speed for the hibernation mode
(p1080 + p2390) * 1.05.
● The value for the activation delay of the cascade control (p2374) must be longer than the
power-up time from the hibernation mode (t
with t
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Cascade control - operating hours
Cascade control - maximum time for continuous mode
Cascade control - absolute operating time limit
Cascade control - switch-off sequence
Define switch-off sequence for an OFF command
Cascade control - motor switch-on delay
Define motor switch-on delay
Cascade control - connect hold time
Define speed hold time after connecting an external motor
Cascade control - motor switch-off delay
Define motor switch-off delay
Cascade control - switch-off speed hold timeDefine speed hold time after dis-
connecting an external motor
= ((p1080 + p2390) * 1.05 * p1120 * p1139) / p1082
y
Advanced commissioning
6.7 Application-specific functions
).
y
299