Line reactor

The line reactor supports the overvoltage protection, smoothes
the harmonics in the line supply and bridges commutation dips.
For the Power Modules subsequently listed, a line reactor is
suitable in order to dampen the specified effects.
Adjacent examples of line reactors.
NOTICE
Damage to the inverter as a result of a missing line reactor
Depending on the Power Module and line supply, if a line reactors is not used, this can
result in damage to the inverter and other components in the electrical plant or system.
• PM240 or PM240-2:
• PM330:
34
6SL3225-0BE25-5AA0,
6SL3225-0BE27-5AA0,
6SL3225-0BE31-1AA0
6SL3310-1PE33-0AA0,
6SL3310-1PE33-7AA0
6SL3310-1PE34-6AA0
6SL3310-1PE35-8AA0,
6SL3310-1PE36-6AA0,
6SL3310-1PE37-4AA0
Install a line reactor if the relative short-circuit voltage of the line supply is below 1%
You must install a line reactor dependent on the relative short-circuit power (fault level)
of the line supply. You can find additional information in Catalog D35.
Power
7.5 kW ... 15.0 kW
Power
160 kW ... 200 kW
250 kW
315 kW ... 400 kW
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Line filter, class B
6SL3203-0BD23-8SA0
Line filter according to
EN 61800-3 Category C2
6SL3000-0BE33-1AA0
6SL3000-0BE35-0AA0
6SL3760-0MR00-0AA0
for
for PM240-2
PM240