Installing
4.6 Installing Control Unit
Changing the function of the terminals
The function of the terminals marked in color in the two diagrams above, can be set.
In order not to have to successively change terminal for terminal, several terminals can be
jointly set using default settings ("p0015 Macro drive unit").
The terminal settings made in the factory described above correspond to the following
default settings:
● Default setting 12 (p0015 = 12): "Standard I/O with analog setpoint"
● Default setting 7 (p0015 = 7): "Fieldbus with data set switchover"
4.6.5
Default setting of the interfaces
Default setting 7: "Fieldbus with data set switchover"
Factory setting for inverters with PROFIBUS or PROFINET interface
DO 0: p0730, DO 1: p0731
Speed setpoint (main setpoint): p1070[0] = 2050[1]
Jog 1 speed setpoint: p1058, factory setting: 150 rpm
Jog 2 speed setpoint: p1059, factory setting: -150 rpm
Designation in BOP-2: FB cdS
88
AO 0: p0771[0], AO 1: p0771[1]
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
DI 0: r0722.0, ..., DI 3: r0722.3
Converter with CU230P-2 Control Units