Permissible line supplies depending on the installation altitude
● Installation altitude up to 2000 m above sea level
– Connection to every supply system permitted for the inverter.
● Installation altitudes between 2000 m and 4000 m above sea level
– Connection to a TN system with grounded neutral point.
– TN systems with grounded line conductor are not permitted.
– The TN line system with grounded neutral point can also be supplied using an
– The phase-to-phase voltage does not have to be reduced.
Note
690 V Power Modules
For 690 V Power Modules, the TN line system must be established with grounded neutral
point through an isolating transformer.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
isolation transformer.
10.3 Restrictions for special ambient conditions
Technical data
429