Status word 1 (ZSW1)
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
If you change over from another telegram to telegram 20, then the assignment of the previous
1)
telegram is kept.
Further information
You can find additional information about Modbus RTU in the "Fieldbuses" Function Manual:
Manuals for the Control Unit
(http://support.automation.siemens.com/WW/view/en/30563628/133300).
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Meaning
1 = Ready to start
1 = Ready
1 = Operation enabled
1 = Fault active
1 = OFF2 inactive
1 = OFF3 inactive
1 = Closing lockout active
1 = Alarm active
1 = Speed deviation within
the tolerance range
1 = Master control request-
ed
1 = Comparison speed
reached or exceeded
1 = Torque limit not reached Comparison value for current or torque has been
Reserved
0 = Alarm, motor over-
temperature
1 = Motor rotates clockwise
0 = Motor rotates counter-
clockwise
0 = Alarm, inverter thermal
overload
Remarks
Power supply switched on; electronics initialized;
pulses locked.
Motor is switched on (ON/OFF1 = 1), no fault is
active. With the command "Enable operation"
(STW1.3), the inverter switches on the motor.
Motor follows setpoint. See control word 1, bit 3.
The inverter has a fault. Acknowledge fault using
STW1.7.
Coast down to standstill is not active.
Quick stop is not active.
It is only possible to switch on the motor after an
OFF1 followed by ON.
Motor remains switched on; no acknowledgement
is necessary.
Setpoint / actual value deviation within the toler-
ance range.
The automation system is requested to accept the
inverter control.
Speed is greater than or equal to the correspond-
ing maximum speed.
fallen below.
--
Internal inverter actual value > 0
Internal inverter actual value < 0
Advanced commissioning
6.2 Inverter control
Signal inter-
connection
in the in-
verter
p2080[0] =
r0899.0
p2080[1] =
r0899.1
p2080[2] =
r0899.2
p2080[3] =
r2139.3
p2080[4] =
r0899.4
p2080[5] =
r0899.5
p2080[6] =
r0899.6
p2080[7] =
r2139.7
p2080[8] =
r2197.7
p2080[9] =
r0899.9
p2080[10] =
r2199.1
p2080[11] =
r0056.13 /
r1407.7
p2080[12] =
r0899.12
p2080[13] =
r2135.14
p2080[14] =
r2197.3
p2080[15] =
r2135.15
191