Default setting 101: "Universal application"
DO 0: p0730, ..., DO 2:
p0732
Additional settings:
Fixed speed setpoint 1: p1001 = 800 rpm
Fixed speed setpoint 2: p1002 = 1000 rpm
Fixed speed setpoint 3: p1003 = 1200 rpm
If several of the DI 3 ... DI 5 = high, the inverter adds the corresponding fixed speeds.
Fixed speed setpoint 15 for essential service mode (ESM): p1015 = 1500 rpm
"Flying restart" is enabled: p1200 = 1
Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26
Designation in BOP-2: P_F 6PA
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
AO 0: p0771[0], AO 1:
p0771[1]
4.6 Installing Control Unit
DI 0: r0722.0, ..., DI 5:
r0722.5
Installing
AI 0: r0755[0]
95