Siemens SINAMICS G120 Operating Instructions Manual page 110

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.6 Installing Control Unit
Integrating inverters into PROFINET
Procedure
To connect the inverter to a control via PROFINET, proceed as follows:
1. Integrate the inverter in the bus system (e.g. ring topology) of the control using
PROFINET cables and the two PROFINET sockets X150-P1 and X150-P2.
The position of the sockets and the pin assignment can be found in Section Overview of
the interfaces (Page 82).
The maximum permitted cable length from the previous station and to the subsequent
one is 100 m.
2. Externally supply the inverter with 24 V DC through terminals 31 and 32.
The external 24 V supply is only required if communications with the control should also
run when the mains voltage is switched off.
You have connected the inverter to the control using PROFINET.
Configuring communication to the control
Configuring the communication using SIMATIC S7 control
You have the following options, if the inverter is not included in the hardware library:
● Install the most up to date STARTER version
● Install the GSDML of the inverter using "Tools/Install GSDML file" in HW Config.
Additional information on this topic is provided in the "Fieldbuses" Function Manual, also see
Manuals for your inverter (Page 451).
Configuring the communication using a non-Siemens control
1. Import the device file (GSDML) of the inverter into the engineering tool for your control
system.
2. Configure the communication.
110
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB