Siemens SINAMICS G120 Operating Instructions Manual page 265

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Figure 6-41
Parameter to set the line contactor control
Parameter
p0860
p0861
r0863.1
p0867
p0869
Line contactor control for PM330 Power Modules
For a PM330, you can connect a line contactor without requiring any additional
parameterization via terminals X9.11 and X9.12. See Digital inputs and outputs on the
PM330 Power Module (Page 66).
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Line contactor control with monitoring
Explanation
Line contactor feedback signal
p0860 = 863.1: No feedback signal
p0860 = 723.x: Feedback signal via DIx
Line contactor monitoring time (Factory setting: 100 ms)
Fault F07300 is output if, for an activated feedback signal, no feedback signal is re-
ceived via the selected digital input after the time set here has expired.
Drive coupling status/control word
Bit to activate the line contactor control: Assign 863.1 to DO x,
Example: Control line contactor via digital output DO 2: p0732 = 863.1
Main contactor holding time after OFF1 (Factory setting: 50 ms)
Time where, after an OFF1, the main contactor remains closed.
Sequence control configuration
p0689 = 0: Line contactor opens immediately for an STO
p0689 = 1: For an STO, the line contactor opens after the time set in p0867 has
expired
Advanced commissioning
6.7 Application-specific functions
265