Siemens SINAMICS G120 Operating Instructions Manual page 121

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

8. Enter the motor data:
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
8.1.
8.2.
8.3.
8.4.
8.5.
8.6.
8.7.
8.8.
8.9.
5.3 Commissioning using a BOP-2 operator panel
Motor type
Depending on the particular inverter, it is possible that the
BOP-2 does not list all of the following motor types.
INDUCT
Third-party induction motor
SYNC
Third-party synchronous motor
RELUCT
Third-party reluctance motor
1L... IND
1LE1, 1LG6, 1LA7, 1LA9 induction motors
1LE1 IND
1LE1☐9 with motor code on the rating plate
100
1PH8 IND
Induction motor
1FP1
Reluctance motor
1F... SYN
1FG1, 1FK7 synchronous motor, without encoder
If you have selected a motor type > 100, then you must enter
the motor code:
With the correct motor code, the inverter assigns the motor
data the following values.
If you do not know the motor code, then you must set the mo-
tor code = 0, and enter the motor data from p0304 and on-
wards from the rating plate.
87 Hz motor operation
The BOP-2 only displays this step if you previously selected
IEC as the motor standard (EUR/USA, P100 = KW 50HZ).
Rated voltage
Rated current
Rated power
Rated frequency
Rated speed
Motor cooling
SELF
Natural cooling
FORCED
Forced-air cooling
LIQUID
Liquid cooling
NO FAN
Without fan
Commissioning
121

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents