Siemens SINAMICS G120 Operating Instructions Manual page 193

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Control word 1 (STW1)
Bit
0
1
2
3
4
5
6
7
8, 9 Reserved
10
11
12
13
14
15
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Meaning
0 = OFF1
0 → 1 = ON
0 = OFF2
1 = No OFF2
0 = Quick stop (OFF3)
1 = No quick stop (OFF3) The motor can be switched on (ON command).
0 = Inhibit operation
1 = Enable operation
0 = Disable RFG
1 = Do not disable RFG
0 = Stop RFG
1 = Enable RFG
0 = Inhibit setpoint
1 = Enable setpoint
0 → 1 = Acknowledge
faults
0 = No control via PLC
1 = Control via PLC
1 = Direction reversal
Reserved
1 = MOP up
1 = MOP down
Reserved
Explanation
The motor brakes with the ramp-down time p1121 of
the ramp-function generator. The inverter switches
off the motor at standstill.
The inverter goes into the "ready" state. If, in addition
bit 3 = 1, then the inverter switches on the motor.
Switch off the motor immediately, the motor then
coasts down to a standstill.
The motor can be switched on (ON command).
Quick stop: The motor brakes with the OFF3 ramp-
down time p1135 down to standstill.
Immediately switch-off motor (cancel pulses).
Switch-on motor (pulses can be enabled).
The inverter immediately sets its ramp-function gen-
erator output to 0.
The ramp-function generator can be enabled.
The output of the ramp-function generator stops at
the actual value.
The output of the ramp-function generator follows the
setpoint.
The inverter brakes the motor with the ramp-down
time p1121 of the ramp-function generator.
Motor accelerates with the ramp-up time p1120 to
the setpoint.
Acknowledge fault. If the ON command is still active,
the inverter switches to"closing lockout" state.
Inverter ignores the process data from the fieldbus.
Control via fieldbus, inverter accepts the process
data from the fieldbus.
Invert setpoint in the inverter.
Increase the setpoint saved in the motorized potenti-
ometer.
Reduce the setpoint saved in the motorized potenti-
ometer.
Advanced commissioning
6.2 Inverter control
Signal inter-
connection
in the in-
verter
p0840[0] =
r2090.0
p0844[0] =
r2090.1
p0848[0] =
r2090.2
p0852[0] =
r2090.3
p1140[0] =
r2090.4
p1141[0] =
r2090.5
p1142[0] =
r2090.6
p2103[0] =
r2090.7
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14