Additional options for wiring the digital inputs
Connecting P-switching contacts with an external pow-
Connecting M-switching contacts with an external pow-
Note
When a contact switching to M is connected, a ground fault at the digital input can lead to the
input being unintentionally controlled.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
er supply
er supply
4.6 Installing Control Unit
You must remove the jumper be-
tween terminals 28 and 69 if it is
necessary to have electrical isolation
between the external power supply
and the internal inverter power sup-
ply.
Remove the jumper between termi-
nals 28 and 69.
Installing
85