Copy protection
In conjunction with the copy protection, the converter settings can be coupled only to a
single, pre-defined hardware.
Know-how protection with copy protection is only possible using the recommended Siemens
card, see also Section: Technical data for CU230P-2 (Page 369)
List of exceptions
The active know-how protection permits an exception list for parameters to be defined that
the customer may access.
If you remove the parameter for the password from the exception list, the know-how
protection can only be undone by reverting to the factory settings.
Actions that are possible during active know-how protection
● Restoring factory settings
● Acknowledging messages
● Displaying messages
● Show message history
● Reading out diagnostic buffer
● Switching to the control panel (complete control panel functionality: Fetch master control,
all buttons and setting parameters)
● Upload (only parameters that are accessible even though know-how protection is active)
The individual parameters that are excluded from the know-how protection can be found in
the List Manual in Chapter "Parameters for write protection and protection of know-how".
Commissioning the converter with know-how protection
Procedure - overview
1. Commission the converter.
2. Create the exception list (Page 330).
3. Activate the know-how protection (Page 328).
4. Save the settings in the converter by copying RAM to ROM with
5. Save the project with
(machine type, password, etc.) that may be required for the support of the end customer.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Backing up data and series commissioning
on the PG/PC. Also back up any other project-related data
7.5 Write and know-how protection
or via p0971 = 1.