Technical data
10.2 Technical data, Power Modules
Table 10- 38 PM240-2, PT, frame sizes C, 3 AC 380 V ... 480 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight without filter
Weight with filter
1) approx. 0.3 kW through the heatsink;
Table 10- 39 PM240-2, IP20, FSD, 3 AC 380 V ... 480 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
400
6SL3211...
...1PE23-3UL0
6SL3211...
...1PE23-3AL0
15.0 kW
39.9 A
32.0 A
11.0 kW
36.0 A
26.0 A
3NE 1817-0 (50 A)
50 A Class J
0.37 kW
18.5 l/s
5.8 kg
6.3 kg
6SL3210-...
...1PE23-8UL0
6SL3210-...
...1PE23-8AL0
18.5 kW
36 A
38 A
15 kW
33 A
32 A
3NE1 818-0 / 63 A
60 A
0.55 kW
0.56 kW
55 l/s
16 kg
17.5 kg
1)
...1PE24-5UL0
...1PE24-5AL0
22 kW
42 A
45 A
18.5 kW
38 A
38 A
3NE1 820-0 / 80 A
70 A
0.68 kW
0.68 kW
55 l/s
16 kg
17.5 kg
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
...1PE26-0UL0
...1PE26-0AL0
30 kW
57 A
60 A
22 kW
47 A
45 A
3NE1 021-0 / 100A
90 A
0.76 kW
0.77 kW
55 l/s
17 kg
18.5 kg