Siemens SINAMICS G120 Operating Instructions Manual page 394

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.2 Technical data, Power Modules
Current derating depending on the pulse frequency
Current derating depending on the pulse frequency
Article number
6SL3210-1PB13-0❒L0
6SL321❒-1PB13-8❒L0
6SL3211-1PB15-5❒L0
6SL3210-1PB17-4❒L0
6SL321❒-1PB21-0❒L0
6SL3210-1PB21-4❒L0
6SL321❒-1PB21-8❒L0
6SL3210-1PC22-2❒L0
6SL3210-1PC22-8❒L0
6SL3210-1PC24-2❒L0
6SL3210-1PC25-4❒L0
6SL3210-1PC26-8❒L0
6SL3210-1PC28-8❒L0
6SL3210-1PC31-1❒L0
The permissible motor cable length also depends on the cable type and the selected pulse fre-
1)
quency.
394
LO base load output current for a pulse frequency of ...
4 kHz
6 kHz
8 kHz
3.2
2.6
2.1
4.2
3.3
2.7
6.0
4.7
3.9
7.4
6.3
5.2
10.4
8.8
7.3
13.6
11.6
9.5
17.5
14.9
12.3
22.0
18.7
15.4
28.0
23.8
19.6
42
35.7
29.4
54
45.9
37.8
68
57.8
47.6
80
68.0
56.0
104
88.4
72.8
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
for 200 V devices
1)
[A]
10 kHz
12 kHz
1.8
1.5
2.3
2.0
3.3
2.8
4.4
3.7
6.2
5.2
8.2
6.8
10.5
8.8
13.2
11.0
16.8
14.0
25.2
21.0
32.4
27.0
40.8
34.0
48.0
40.0
62.4
52.0
Converter with CU230P-2 Control Units
14 kHz
16 kHz
1.4
1.2
1.8
1.6
2.5
2.2
3.3
3.0
4.7
4.2
6.1
5.4
7.9
7.0
9.9
8.8
12.6
11.2
18.9
16.8
24.3
21.6
30.6
27.2
36.0
32.0
46.8
41.6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents