Siemens SINAMICS G120 Operating Instructions Manual page 418

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.2 Technical data, Power Modules
Relationship between pulse frequency and current reduction
Table 10- 58 Current reduction depending on pulse frequency
Rated
Power
(LO)
418
Base load
Base load current (LO) at pulse frequency of
current
(LO)
4 kHz
6 kHz
kW
A
7.5
18.0
11
25.0
15
32.0
18.5
38.0
22
45.0
30
60.0
37
75.0
45
90.0
55
110
75
145
90
178
8 kHz
10 kHz
A
A
12.5
11.9
18.1
17.1
24.7
23.4
32.3
26.6
38.3
31.5
51.0
42.0
63.8
52.5
76.5
63.0
93.5
77.0
123
102
151
125
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
12 kHz
14 kHz
A
A
10.6
9.20
15.2
13.3
20.8
18.2
22.8
19.0
27.0
22.5
36.0
30.0
45.0
37.5
54.0
45.0
--
--
--
--
--
--
Converter with CU230P-2 Control Units
16 kHz
A
A
7.90
6.60
11.4
9.50
15.6
12.8
17.1
15.2
20.3
18.0
27.0
24.0
33.8
30.0
40.5
36.0
--
--
--
--
--
--

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents