Commissioning
5.3 Commissioning using a BOP-2 operator panel
Select a suitable application class
When selecting an application class, the inverter appropriately sets the closed-motor control.
Application class
Motors that can be
operated
Power Modules
that can be oper-
ated
Application exam-
•
ples
Properties
•
•
•
•
Max. output fre-
quency
Torque control
Commissioning
•
•
128
Standard Drive Control
Induction motors
PM240, PM240-2
Pumps, fans, and compressors with flow
characteristic
Typical correction time after a speed change:
100 ms ... 200 ms
Typical correc-
tion time after
a load surge:
500 ms
Standard
Drive Control
is suitable for
the following
requirements:
–
Motor
power ratings < 45 kW
–
Ramp-up time 0 → Rated speed (de-
pendent on the rated motor power):
1 s (0.1 kW) ... 10 s (45 kW)
–
Applications with constant load torque
without load surges
Standard Drive Control is insensitive with
respect to imprecise setting of the motor da-
ta
550 Hz
Without torque control
Contrary to "Dynamic Drive Control", a
speed controller does not have to be set
When compared to "Configuration for ex-
perts"
–
Simplified commissioning using preas-
signed motor data
–
Fewer parameters
Dynamic Drive Control
Induction, synchronous and reluctance motors
PM240, PM240-2, PM330
Pumps and compressors with displacement
•
machines
Typical correction time after a speed change:
•
< 100 ms
Typical correction
•
time after a load
surge: 200 ms
Dynamic Drive
•
Control controls
and limits the mo-
tor torque
Torque accuracy
•
that can be
achieved: ± 5 %
for 15 % ... 100 % of the rated speed
We recommend Dynamic Drive Control for the
•
following applications:
–
Motor power ratings > 11 kW
–
For load surges 10 % ... >100 % of the rat-
ed motor torque
Dynamic Drive Control is necessary for a ramp-
•
up time 0 → rated speed (dependent on the rat-
ed motor power):
< 1 s (0.1 kW) ... < 10 s (250 kW).
Speed control with lower-level torque control
Fewer parameters when compared to "Configu-
•
ration for experts"
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
240 Hz