Wiring Terminal Strips - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.6 Installing Control Unit
4.6.6

Wiring terminal strips

Danger to life as a result of hazardous voltages when connecting an unsuitable power
supply
Death or serious injury can result when live parts are touched in the event of a fault.
• For all connections and terminals of the electronic boards, only use power supplies that
In order to install the inverter in compliance with UL, you may only connect the DO 0 and
DO 2 relay outputs of the Control Unit using copper wires approved for 75 °C.
Danger to life as a result of a hazardous voltage at the Control Unit
If the insulation is damaged on the lines that are connected to the terminals DO 0 and DO
2, parts of the Control Unit may still be connected to the power supply. When connecting
higher voltages at terminals DO 0 and DO 2, there is a risk of electric shock when touching
the Control Unit.
• Only connect dangerous voltages using cables with double insulation at relay outputs
NOTICE
Damage to the inverter when using long signal cables
Using long cables at the inverter's digital inputs and 24 V power supply can lead to
overvoltage during switching operations. Overvoltages can damage the inverter.
• If you use cables of more than 30 m at the digital inputs and 24 V power supply, connect
Table 4- 20
Solid or finely-stranded conduc-
Cables with twin end sleeves are not permissible.
106
WARNING
provide PELV (Protective Extra Low Voltage) or SELV (Safety Extra Low Voltage)
output voltages.
DANGER
DO 0 and DO 2 of the Control Unit.
an overvoltage protection element between the terminal and the associated reference
potential.
We recommend using the Weidmüller overvoltage protection terminal with designation
MCZ OVP TAZ DIODE 24VDC.
Permissible cable and wiring options
tor
Finely-stranded conductor with
non-insulated conductor end
sleeve
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Finely-stranded conductor with
partially insulated conductor end
sleeve
Converter with CU230P-2 Control Units

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents