Parameter
r0056.15
p0210
p1240
p1245
r1246
p1247
p1255
p1257
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Description
Status word closed-loop control
0 signal
V
controller is not active
DC min
1 signal
V
controller is active (kinetic buffering)
DC min
Device supply voltage (factory setting: 400 V)
V
controller configuration (factory setting: 1)
DC
0
Inhibit V
controller
DC
1
Enable V
controller
DC max
2
Enable V
controller (kinetic buffering)
DC min
3
Enable V
controller and V
DC min
V
controller activation level (kinetic buffering) (factory setting: 76 %)
DC min
V
controller activation level[V]
DC min
r1246 = p1245 × √2 × p0210
V
controller dynamic factor (factory setting: 300 %)
DC min
V
controller time threshold (factory setting: 0 s)
DC min
Maximum duration of the kinetic buffering If kinetic buffering lasts longer than that
specified in the parameter value, the inverter outputs fault F7406.
A value of 0 deactivates the monitoring.
V
controller speed threshold (factory setting: 50 rpm)
DC min
When fallen below, the inverter outputs fault F7405.
Advanced commissioning
6.7 Application-specific functions
controller
DC max
263