Siemens SINAMICS G120 Operating Instructions Manual page 140

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning
5.4 Commissioning with a PC
Configuring the drive
Procedure
To configure the drive, proceed as follows:
1.
Select a suitable application class
When selecting an application class, the inverter appropriately sets the closed-motor control.
Application class
Motors that can be
operated
Power Modules
that can be oper-
ated
Application exam-
ples
Properties
140
When selecting an application class, the inverter assigns the motor con-
trol with the appropriate default settings:
• [1] Standard Drive Control (Page 141)
• [2] Dynamic Drive Control (Page 142)
• [0] Expert - or if no application class is listed:
→ Configuration for experts (Page 143)
Standard Drive Control
Induction motors
PM240, PM240-2
Pumps, fans, and compressors with flow
characteristic
Typical correction time after a speed change:
100 ms ... 200 ms
Typical correc-
tion time after
a load surge:
500 ms
Standard Drive
Control is suit-
able for the fol-
lowing
requirements:
Motor
power ratings < 45 kW
Ramp-up time 0 → Rated speed (de-
pendent on the rated motor power):
1 s (0.1 kW) ... 10 s (45 kW)
Applications with constant load torque
without load surges
Standard Drive Control is insensitive with
respect to imprecise setting of the motor da-
ta
Dynamic Drive Control
Induction, synchronous and reluctance motors
PM240, PM240-2, PM330
Pumps and compressors with displacement
machines
Typical correction time after a speed change:
< 100 ms
Typical correction
time after a load
surge: 200 ms
Dynamic Drive
Control controls
and limits the mo-
tor torque
Torque accuracy
that can be
achieved: ± 5 %
for 15 % ... 100 % of the rated speed
We recommend Dynamic Drive Control for the
following applications:
Motor power ratings > 11 kW
For load surges 10 % ... >100 % of the rat-
ed motor torque
Dynamic Drive Control is necessary for a ramp-
up time 0 → rated speed (dependent on the rat-
ed motor power):
< 1 s (0.1 kW) ... < 10 s (250 kW).
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB