General Data, Pm240-2 - 400V - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

10.2.2.3

General data, PM240-2 - 400V

Property
Line voltage
Output voltage
Input frequency
Output frequency
Line impedance
Power factor λ
Inrush current
Overvoltage category acc.
to EN 60664-1
Pulse frequency
Short-circuit current rating
(SCCR)
Electromagnetic compati-
bility according to IEC/EN
61800-3
Braking methods
Degree of protection ac-
cording to EN 60529
Ambient temperature for
Ambient conditions accord-
ing to EN 60721-3-3
Temperature during stor-
age according to EN
60721-3-3
Cooling air
Relative humidity
Pollution according to EN
61800-5-1
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Version
FSA ... FSC
380 V ... 480 V 3-ph. AC ± 10 %
FSD ... FSE
3 AC 380 V ... 480 V -20 %, +10 %
3 AC 0 V ... 0.95 x input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
Uk ≥ 1 %, for lower values, we recommend a line reactor, or a Power Module with the next
higher power rating.
FSA ... FSC
0.7 without line reactor for Uk ≥ 1 %
0.85 with line reactor for Uk < 1 %
FSD ... FSE
0.95 (line reactor not required)
< LO base load input current
The inverter insulation is designed for surge voltages according to overvoltage Category III.
4 kHz (factory setting)
Can be adjusted in 2 kHz steps in the range from 2 kHz ... 16 kHz.
Restriction: from a LO base load power of 55 kW up to 8 kHz.
The output current is reduced if you increase the pulse frequency.
≤ 65 kA rms
Devices with integrated filter are suitable for Category C2 environments.
DC braking, compound braking, dynamic braking with integrated braking chopper
Chassis devices
IP20
PT devices
IP20, IP54
LO base load power without derating:
HO base load power without derating:
LO/HO base load power with derating:
Details see Section Power-dependent data, PM240-2 - 400 V (Page 397).
For the maximum permissible ambient temperature, also observe the permissible ambient
temperatures for the Control Unit and possibly operator panel (IOP or BOP-2) .
FSA ... FSC:
Protected against damaging chemical substance, according to environmental
Class 3C2
FSD ... FSE
Protected against damaging chemical substance, according to environmental
Class 3C3
-40 °C ... +70 °C
clean and dry air
< 95% - condensation not permissible
suitable for environments with degree of pollution 2
10.2 Technical data, Power Modules
Must be installed in a control cabinet
Must be installed in a control cabinet
at the control cabinet panel
-20 °C ... +40 °C
-20 °C ... +50 °C
-20 °C ... + 60° C
Technical data
395

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents