Power-dependent data, PM330

Note
Recommended connection cross-sections
The recommended connection cross-sections are determined for copper cables at 40° C
(104° F) ambient temperature and cables with a permitted operating temperature on the
conductor for 70° C (laying type C - factor for bundling 0.75 considered) according to DIN
VDE 0298-4/08.03).
Protective conductor cross-section (S: Cross-section of the supply connection phase
conductor, MS: Cross-section of the external protective conductor):
Minimum cross-sections:
• S < 16 mm² → MS = S
• 16 mm² ≤ S ≤ 35 mm² → MS = 16 mm²
• S > 35 mm² → MS = 0.5 × S
Recommended cross-sections:
• MS ≥ S
424
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB