Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning
5.3 Commissioning using a BOP-2 operator panel
Procedure when using the BOP-2 operator panel
To start the motor data identification, proceed as follows:
1.
2.
3.
4.
5.
6.
You have now completed motor data identification.
134
Press the HAND/AUTO key. The BOP-2 displays the symbol for
manual operation.
Switch on the motor.
The motor data identification takes several seconds.
Wait until the inverter switches off the motor after motor data identi-
fication has been completed.
If you have also selected a rotating measurement in addition to the
motor data identification, then the inverter again issues the alarm
A07991.
Switch the motor on again in order to optimize the rotating meas-
urement.
Wait until the inverter switches off the motor after completion of the
optimization. The optimization time depends on the rated motor
power: 20 s ... 2 min.
Switch the inverter control from HAND to AUTO.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB