Dimensions, Hole Drilling Templates, Minimum Clearances, Tightening Torques - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.4 Installing Power Modules
4.4.1

Dimensions, hole drilling templates, minimum clearances, tightening torques

Dimensions and drilling patterns for the PM230 Power Modules, IP55
Table 4- 1
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
Depth with
1)
- BOP-2/blanking cover + 7 mm;
- IOP + 17 mm
Table 4- 2
Frame size
FSA, FSB
FSC
FSD, FSE, FSF
Mounting and operation are permissible without lateral clearance. For tolerance reasons we rec-
1)
ommend a lateral clearance of approx. 1 mm.
Mounting up to an ambient temperature of 40 °C in operation without lateral clearance is permissi-
2)
ble. For tolerance reasons, we recommend a clearance of approx. 1 mm.
58
Dimensions
Dimensions (mm)
a
(width)
(height)
154
460
180
540
230
620
320
640
320
751
410
915
Mounting hardware and clearances to other devices
Hardware
M4 screws
M5 screws
M8 screws
b
c
(depth)
1)
249
249
249
329
329
416
Tightening torque
(Nm)
2.5
2.5
13
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Drilling dimensions
d
e
132
445
158
524
208
604
285
600
285
710
370
870
Clearances (mm)
Top
Bottom
100
100
125
125
300
300
Converter with CU230P-2 Control Units
f
11
11
11
17.5
17.5
17.5
Lateral
0
1)
0
1)
50
2)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents