Parameter
p1213[1]
Additional information is provided in the parameter list of the List Manual.
Advanced settings
If you with to suppress the automatic restart function for certain faults, then you must enter
the appropriate fault numbers in p1206[0 ... 9].
Example: p1206[0] = 07331 ⇒ No restart for fault F07331.
Suppressing the automatic restart only functions for the setting p1210 = 6, 16 or 26.
Danger to life if an OFF command has no effect.
When the inverter is only controlled via the fieldbus interface, the motor restarts with the
setting p1210 = 6, 16, 26 – even if the communication link is currently interrupted. When
communication is interrupted, the control system cannot switch off the motor.
• Enter the fault number of the communication error in parameter p1206.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Explanation
Automatic restart monitoring time
to reset the fault counter (factory setting: 0 s)
This parameter is only effective for the settings p1210 = 4, 6, 14, 16, 26.
Using this monitoring time, you prevent that faults, which continually occur within a
certain time period, are automatically acknowledged each time.
The monitoring function starts with a successful start attempt and ends after the moni-
toring time has expired.
If, during the monitoring time p1213[1], the inverter made more successful starting at-
tempts than defined in p1211, the inverter interrupts the automatic restart function and
signals fault F07320. To switch on the motor again you must acknowledge the fault and
switch on the inverter (ON/OFFS1 = 1).
WARNING
Example:
Fault number F01910 means: Communication via PROFIBUS failed.
Set p1206[n] = 1910 (n = 0 ... 9).