Technical data
10.1 Technical data for CU230P-2
Feature
Analog inputs
Digital outputs /relay out-
puts
Analog outputs
Motor temperature sensor PTC
USB interface
Dimensions (W × H × D)
Memory card (optional)
Weight
Operating temperature
370
Data / explanation
4 (AI 0 ... AI 3)
3 (DO 0 ... DO 2)
2 (AO 0 ... AO 1)
KTY84
Temperature switch with isolated contact
Mini-B
73mm × 199mm × 50mm
Slot for SD or MMC memory cards, see also Section: Control Units (Page 27)
0.61kg
-10 °C ... 60 °C
-10 °C ... 55 °C
0° C ... 50° C
Observe any possible restrictions regarding the operating temperature as a result of the Power
Module.
Differential inputs
12-bit resolution
13 ms response time
AI 0 and AI 1 can be switched over:
0 V ... 10 V or -10 V ... +10 V (voltage < 35 V)
0 mA ... 20 mA (120 Ω input resistance, voltage < 10 V,
current < 80 mA)
If AI 0 and AI 1 are configured as supplementary digital in-
puts: Voltage < 35 V, low < 1.6 V, high > 4.0 V, 13 ms ± 1 ms
response time for debounce time p0724 = 0.
AI 2 can be switched over:
0 V ... 10 V or -10 V ... +10 V (voltage < 35 V)
0 mA ... 20 mA (voltage < 10 V, current < 80 mA)
Temperature sensor Pt1000/LG-Ni1000/DIN-Ni1000
(characteristics: See below)
AI 3:
Temperature sensor Pt1000/LG-Ni1000/DIN-Ni1000 (charac-
teristics: See below)
DO 0, DO 2: 30 VDC 5 A / 250 VAC, 2 A
DO 1: 30 V DC 0.5 A
2 ms update time
0 V ... 10 V or 0 mA ... 20 mA
Reference potential: "GND"
16-bit resolution
4 ms update time
Short-circuit monitoring < 20Ω
Overtemperature 1650Ω
Short-circuit monitoring < 50 Ω
Wire breakage: > 2120 Ω
Depth when mounting on the Power Module
CU230P-2 HVAC, CU230P-2 CAN and CU230P-2 DP
Without inserted operator panel
CU230P-2 PN without inserted operator panel
With inserted BOP-2 or IOP operator panel
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
1)
Converter with CU230P-2 Control Units

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents