Program blocks
5.10 Switch and relay blocks
Parameters
Parameters
Input parameters
En
Trigger
Function parameters
Pulse duration (ms)
Interpulse period (ms)
Cycles
Start value
End
Output parameters
Output
320
Tag type / range of
Description
values
Enable parameter, see section Often used parame-
ters (Page 252).
True / False
When there is an edge change 0 → 1 a new pulse
sequence begins.
Digital input / output /
bit memory
With the setting "True", the pulse sequence set in
the parameters runs precisely once after the RTU
STATUS_ERROR
starts up or after a new configuration has been
adopted.
With the setting "False" the output is never set.
100 .. 999999999
Pulse duration in milliseconds
0 .. 999999999
Pause between two pulses in milliseconds
If the number of pulses is > 1 or the Start value
"Pause" is selected, the Interpulse period must be ≥
100 ms.
1 .. 999999999
Specifies the number of pause/pulse cycles (pulse
sequence).
Pulse
Pause
Trigger
Time
Digital output / bit
Tag in which the value calculated by the block is
memory
output.
With "Pulse" the pulse sequence starts with a
"1" at the output.
With "Pause" the pulse sequence starts with a
"0" at the output.
With "Trigger", the pulse sequence ends as
soon as the "Trigger" input changes to 0 or the
configured number of cycles is reached.
With "Time" the pulse sequence ends when it
has run completely.
Operating Instructions, 06/2019, C79000-G8976-C382-06