Siemens Simatic RTU303xC Series Operating Instructions Manual page 267

Telecontrol rtu
Table of Contents

Advertisement

Tr
Ton
R
Q
Figure 5-5
Parameters
Parameters
Input parameters
En
Trigger
Reset
Function parameters
On delay (ms)
Output parameters
Output
RTU303xC
Operating Instructions, 06/2019, C79000-G8976-C382-06
Trigger
On delay
Reset
Output
Circuit diagram of a block. "Retentive on delay"
Range of values
True / False
Digital input /
output / bit
memory
STATUS_ERROR
True / False
Digital input /
output / bit
memory
STATUS_ERROR
100 .. 999999999
Digital output / bit
memory
Description
Enable parameter, see section Often used parameters
(Page 252).
When there is an edge change 0 → 1 the time of On
delay is started.
With the setting "True" the trigger is always active.
With the setting "False" the block is never processed.
When there is an edge change 0 → 1 at the "Reset" input
after the On delay ( = 1) has elapsed the output is reset
to 0.
With the setting "True" the input is always active and the
output is set to 0 immediately. The function is therefore
actually turned off.
With the setting "False" the input is never active.
On delay in milliseconds
After the time of the On delay has elapsed, the output is
set to 1.
Tag in which the value calculated by the block is output.
Program blocks
5.6 Blocks for time functions
267