Parameters
Parameters
Input parameters
En
Trigger
Reset
Function parameters
On delay (ms)
On delay max.
(ms)
Off delay min
(ms)
Off delay max.
(ms)
Output parameters
Output
5.6.7
Pulse sequence
Function
A maximum of 2 blocks of this type can be created.
A repetitive pulse sequence with configurable duration of the individual high and low phases
is sent to the output. The phase position of the first phase is always high. If the pulse
sequence is to begin with the phase position "Low", the first phase can also be configured
with the duration 0 or the output can be negated.
RTU303xC
Operating Instructions, 06/2019, C79000-G8976-C382-06
Range of values
Description
Enable parameter, see section Often used parameters
(Page 252).
When there is an edge change 0 → 1 the On delay is
True / False
•
started.
Digital input /
•
When there is an edge change 1 → 0 the Off delay is
output / bit
started.
memory
With the setting "True" the trigger is always active.
STATUS_ERROR
•
With the setting "False" the block is never processed.
When there is an edge change 0 → 1 On delay is
True / False
•
stopped and the output is set to 0. As long as the input is
Digital input /
•
set to 0, the value of "Trigger" is ignored.
output / bit
When there is an edge change 1 → 0 the block can be
memory
processed again.
STATUS_ERROR
•
With the setting "True" an edge change 0 → 1 at "Trigger"
is permanently ignored. The "Off delay " function is there-
fore also turned off.
With the setting "False" the input is never active.
100 .. 999999999
Minimum time in the clock cycle during which the output
= 1.
100 .. 999999999
Maximum time in the clock cycle during which the output
= 1.
100 .. 999999999
Minimum time in the clock cycle during which the output
= 0.
100 .. 999999999
Maximum time in the clock cycle during which the output
= 0.
Tag in which the pulses generated by the block are out-
Digital output / bit
•
put.
memory
Program blocks
5.6 Blocks for time functions
269